You should start by downloading the app to perform the start-up. This is available for iPhone and Android, and is called TROX Ox ServiceApp.
There is a user app for iPhone and Android, respectively, called TROX Ox.
Both apps use the camera to scan QR codes to connect to FAM-W, and the connection is made via Bluetooth. You must therefore give the apps access to these functions on your phone.
When you have a SystemController in the system, it must be the Root Node in the mesh system, so you must start by scanning the QR code for the mesh system on the SystemController. This ensures that all devices belong to the same system. Open the TROX Ox ServiceApp on your phone and select System Integration. All FAM-W units that are brand new or have been set up in the mesh system will appear in the app.
When FAM-W is set to stand-alone mode, each FAM-W creates its own small network, with FAM-W as the root node.
To reduce battery consumption, wireless sensors and actuators only communicate directly with FAM-W. Mesh technology therefore only works between FAM-W devices.
The battery-powered components connected to the FAM-W have a minimum battery life of 7 years.
To save battery power, the display on the control panel is turned off during normal operation. To wake up the display, either turn the wheel or press the button to the right of the wheel.
To achieve long battery life, the CO2 sensor remains dormant for periods of 2 minutes. This means that the sensor is activated every 2 minutes, takes a measurement, and transmits this value to the FAM-W. Other values such as temperature and relative humidity are measured continuously and transmitted to the FAM-W once per minute.
FAM-W is set up to communicate with SystemController once per minute. This is to reduce traffic in the system. If FAM-W has a VAV damper that is in a working range that requires it to control the fans (between 70–100% damper angle and measuring air), FAM-W communicates all values every 10 seconds.
No, only values that have a natural variation are transferred every minute. These include, for example, air volume, temperature, CO2, damper angle, etc. Values such as Vmin, Vmax, sensor types, etc. are not transferred. If you change these settings, FAM-W will notify the SystemController that the configuration has been changed, and the SystemController will request a complete overview.
Yes, this is possible. Use the TROX Ox ServiceApp, select System Integration, and scan the QR code on the SystemController. When you get to the next screen, press the + sign at the bottom of the screen and scan QR code 2 on the FAM-W box (the one on the label on the box). The FAM-W will transfer the Mesh settings to the SystemController and restart.
One QR code is marked with the number 2 to indicate QR code no. 2. This is used with the TROX Ox ServiceApp to change the configuration of the FAM-W. The other QR code has a mark with the number 3 to indicate QR code no. 3. This is used with the TROX Ox app (user app) to change the temperature setting for the room.
QR code 1 = QR code in SystemController
QR code 2 = QR code for TROX Ox ServiceApp
QR code 3 = QR code for TROX Ox (user app)
When FAM-W is brand new (has not been set up), it is open for anyone to connect to. This is because we assume that setup will be done immediately after the devices have been powered up. Once the devices have been set up with their settings, we do not want anyone with the TROX Ox ServiceApp to be able to change the settings, which is why you have to scan QR code 2 to access the device.
If you have access to the SystemController and its Mesh ID, we assume that you should have access to make changes to the settings in FAM-W – and therefore you do not need to scan QR code 2 for this.
When you have set up FAM-W in a system, you must scan the QR code on SystemController to see all the devices. This is done to prevent unauthorised persons from accessing the devices.
If someone else is communicating with FAM-W using the TROX Ox ServiceApp or TROX Ox (user app), others will not be able to connect. FAM-W can only be connected to one mobile device at a time.
Unfortunately, Bluetooth technology can be a bit unpredictable at times. If you are unable to connect, try closing the app completely and restarting it.
It may be that the Bluetooth communication is stuck on the previous FAM-W even though the app says otherwise (the yellow light on the previous FAM-W is lit). By turning off Bluetooth on your phone, closing the app and restarting Bluetooth and the app, you will probably be able to continue.
By deleting the content on the NFC card, you can perform a factory reset of the FAM-W. It is recommended to disconnect the FAM-W from the power supply before deleting the contents of the card – this ensures that the FAM-W boots from an empty card and is thus factory reset. The card can be deleted using the TROX Ox ServiceApp.
The NFC card can be removed from the box and reset by holding the card against the phone while using the function in the TROX Ox ServiceApp to reset the device. Ensure that the NFC card is installed correctly and that all connection pins are inserted correctly.
It is up to each installer/building owner to decide where to place the QR codes. QR code 3 is used to change the temperature setpoint in the room, and we recommend placing the code in the door frame leading into the room if this is natural – or in a suitable place in the room. QR code 2 must be used to make settings on the FAM-W if the system is in Stand-Alone mode, and in this case it is advisable to place an extra QR code on the ceiling profile where the box is located, or on a list that is accessible to qualified personnel.
In the TROX Ox ServiceApp, you can save up to five different settings in a small library, allowing you to easily copy the settings to another room. Please note that wireless components are not copied and must be connected to the FAM-W in each room.
The settings for the FAM-W boxes are stored on the NFC card. By swapping cards between rooms, you can move the settings from one room to another.
If FAM-W is in two-room mode with a setup for each room, the settings in room 1 will be retained as settings for FAM-W if you switch to single-room mode.
The wireless components will take some time to connect and transfer information, so it is recommended to start with these. Then add components such as VAV dampers, actuators for heating and cooling, etc.
You can proceed to the next room without the wireless components being fully connected to the FAM-W unit. It is easy to go back and check that the values are correct at a later time.
When connecting wireless components, the mesh information must be transferred from the FAM-W to the component via Bluetooth communication, then the component must restart and the information is transferred. Since information is transferred once per minute, it may take almost a minute for the information to be transferred, depending on when you hit the interval with the connection.
Unfortunately, this is a bug in the app that occurs from time to time. If you go back one step and then back again, it will usually resolve itself. As a last resort, disconnect from FAM-W and then reconnect and try again.
Check the actuator to see if it is set to Modbus communication (and not analogue communication) and if it has the correct Modbus address. Extraction dampers should have addresses 1-10 (starting at address 1), and supply air should have addresses 11-20 (starting at address 11). Modbus must have a baud rate of 38400 and a transmission format of 1-8-N-1.
If FAM-W communicates with the VAV dampers via Modbus, FAM-W will read the nominal air volume, as well as Vmin and Vmax from the damper. If FAM-W communicates with the VAV dampers via analogue 0-10 V signals, all information must be entered into FAM-W.
In order for FAM-W to recognise the X-SENS TPDM sensor, it must have Modbus address 125 or 126 (starting at 125). This can be set via the X-SenseNFC app (Android only). Modbus must have a baud rate of 38400 and a transmission format of 1-8-N-1.
In order for FAM-W to recognise the CP-RCNE control panel, it must have Modbus address 91 or 92 (starting at 91), and the device must be set to Modbus communication. This can be set via the Belimo Assistant 2 app. Modbus must have a baud rate of 38400 and transmission format 1-8-N-1.
Modbus must have a baud rate of 38400 and a transmission format of 1-8-N-1. The correct Modbus address for each component can be found in the IOM manual for FAM-W.
If you have a FAM-W MOD2, each Modbus output will be a separate loop. This means that you can have a supply air damper for each output, both of which have Modbus address 11.
Equipment with Modbus communication and the correct Modbus setting can be identified automatically by the FAM-W. Connect to the FAM-W via the TROX Ox ServiceApp, press the three dots in the upper right corner and select "Auto Detect Components". Components that require analogue communication (or digital input) or wireless communication (such as wireless sensors) must be set up manually.
When connected to a FAM-W, you can choose to set the device to "Air volume override" via the three dots in the upper right corner. This will bring up a page where you can override the VAV damper, cooling output and heating output to a specific value (0-100%) until you reset this function again. This should make it possible to regulate the air volume on valves, set the correct pressure for the fan, ventilate water systems, etc.
A Modbus output can operate 2 actuators + 1 sensor or control panel. The limitation lies in the power consumption of the equipment. The maximum power consumption for an output is 7 W.
Since the starting current of a thermoelectric actuator is close to the maximum power consumption for an output, only one actuator can be connected per output. If you have a free output, it can be configured to control a thermoelectric actuator. It does not matter whether the output is designed for Modbus communication, is configurable, or can be used for an EM module. If the output is used to control a thermoelectric actuator, no other components can be connected to this output.
The FAM-W can control the EM-RM relay module to regulate heating or cooling requirements, thereby controlling 230 V thermoelectric actuators.
Each FAM-W can have 4 actuators connected (4 different addresses). If devices can be controlled in parallel and do not exceed the maximum current draw for the output, then more can be connected. For many actuators, the EM-RM relay module can be used.
Actuators for controlling water valves can be of the "thermoelectric" or "motorised" type. Devices that are typically mounted on a radiator are normally of the thermoelectric type. This means that the current draw is like a normal thermoelectric on/off regulator at full power, and only one per output can be used. Motorised actuators are often located above the ceiling on a manifold for heating or cooling and have a much lower current draw. Here, several actuators can be connected in parallel to one output without exceeding the maximum current draw.
Using an expansion module with a relay, EM-RM, FAM-W can control the lighting on/off. A PIR sensor or light switch can be used to control the lighting. The PIR sensor can be located in the X-SENS TPDM connected to FAM-W via Modbus, or be an external PIR sensor connected via a digital input.
FAM-W can only control lighting on/off based on a digital input. It is not possible to dim the lighting via FAM-W.
If FAM-W has several temperature sensors connected, FAM-W will regulate based on an average of these sensors. The same applies if the unit has several sensors for CO2 and/or relative humidity. You can choose to control only selected sensors by deactivating sensors via the TROX Ox ServiceApp.
A configurable output (T2 and T3 for FAM-W MOD1, and T3 for FAM-W MOD2) has two inputs and outputs. Each of these can be used for two analogue inputs and outputs for a VAV damper (0-10 V output to control air volume and 0-10 V input to read actual air volume), for two digital inputs (key card holder, light switch, external PIR sensor), or one of each. In the TROX Ox ServiceApp, select connection 2.1 and 2.2 (for output T2) and 3.1 and 3.2 (for output T3) respectively.
Communication between FAM-W and the EM modules takes place via I2C bus communication, and the units can be connected in a daisy chain. This means that each device must be given a unique address (done via dip switch in the EM device). Only output T4 can be used for EM modules.
If the VAV damper has Modbus communication, set the dampers to the correct setting and connect them to FAM-W via output T1. If the VAV damper only has analogue communication, connect the dampers via a configurable output (T2 and T3 for FAM-W MOD1, and T3 for FAM-W MOD2). The room is then equipped with a wireless sensor or control panel and a wireless actuator for the radiator.
FAM-W only has connection points for RJ45 data cables, so to connect components without such a connection, use the ADP-MOD-SPC adapter (Adapter – Modbus – connection terminals).
To connect a thermoelectric actuator, use the ADP-AD-SPC adapter (Adapter – analogue/digital – connection terminals).
Yes, the only difference between ADP-AD-SPC and ADP-MOD-SPC is that the MOD variant has two RJ45 connectors. If you use the MOD variant to connect analogue equipment, you only need to connect to one of the RJ45 connectors.
When you have an overview of all FAM-W boxes in the overview, you will find an "Identify" button for identification. Pressing this button will cause the yellow light on the box to flash and a beep will be emitted from the specific box. This makes it easy to find the correct box.
A green flashing light means that the box has not been set up; it is like "factory new". Once it has been set up, either in a system with a system controller or in stand-alone mode, the light will remain green.
If you do not have a light on or a flashing light, the device is dead. This may be because the device is not receiving power or is defective. Check the power supply before contacting support.
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
We are here for you
Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265